Enviro Test Construct Pipe Cable Fault Location System

Enviro Test Construct low voltage pipe cable fault location system has although low voltage cable and distribution cable have relatively low voltage.

SKU: ETCBDGFL-209 Category:

Overview

Enviro Test Construct low voltage pipe cable fault location system has although low voltage cable and distribution cable have relatively low voltage, the fault’s location is more difficult than HV cable because of the larger quantity lines and bad environment. Because of common HV surge generator’s high output is over the max withstand voltage of LV cable, which is very easy to cause new faults. T8 overcomes this problem effectively. The max output is 15 kV, but max impulse energy up to 900J which can protect the LV cable and make the recharge sound loud enough.

 

Technical Specifications

DC Voltage Output0 kV to 15 kV continuously adjustable
Output PowerPeak 2000 W
Capacitance8 μf
Max Discharge Energy900 J
Power SupplyLithium battery
Size19.7 in x 12 in x 18 in (500 mm × 305 mm × 457mm)
Weight65 lb (29.5 kg)
Low Voltage Impulse Launching Voltage30 V
Sampling Frequency200 MHz
Max Ranging Scope100 km
Dead Zone2m
Max Resolution0.4 m
Power SupplyAC 220 V, 50 Hz
Size10.7 in x 8.5 in x 3.1 in (274 mm × 218 mm × 81 mm)
Weight7.7 lb (3.5 kg)
Precision Of Point Positioning0.1 m
Precision Of Path Location0.1 m
Precision Of Step Voltage Method0.1 m
Anti-noise mode: Strong noise reduction mode
Work ModeBackground suppression noise reduction mode
Point location mode: Intelligent Acosto-Magnetic Time Difference Mode
Display ModeColour LCD
PowerLi-battery, 12 h standby