Enviro Test Construct pH Power Meter – Accuracy class of 0.1 % or 0.2 %

The pH Power Meter provides precise pH measurements with an accuracy class of 0.1% or 0.2%, ensuring reliable and accurate water quality testing.

SKU: ETCPHM-281 Category:

Overview

Enviro Test Construct pH Power Meter – Accuracy class of 0.1 % or 0.2 % is a single phase handheld electronic meter test, used for testing single phase electricity meters error on site. Wide measurement ranges from 1mA to 120 A and 0 V to 600 V, and can be used to test alternating current parameters – voltage, current, active power, reactive power, apparent power, harmonics, phase angle, power factor, frequency, energy, etc.

 

Features

  • Rotary filed indication
  • Vector diagram display
  • External thermal-printer
  • 4-quadrant measurement
  • Display of vector diagram
  • Energy meter counters testing
  • Testing of energy and power registers
  • Testing of 1P2W electricity meter error
  • Testing of 1P2W inductive energy meter error
  • Testing of 1P2W mechanical energy meter error
  • Oscilloscope function displays current and current wave
  • Frequency, phase angle and power factor measurement
  • Harmonic analysis for voltage and current up to the 63th harmonics
  • Power and energy measurement of active, reactive and apparent energy

 

Technical Specification

Accuracy class0.1 % or 0.2 %
Active power measurement accuracy0.1 %, 0.2 %
Energy measurement accuracy0.1 %, 0.2 %
Power supplyAAA type, Li rechargeable battery, 2700 mAh, 3.6 V it can work 48 hours continuously
Warming-up time< 2 min
Voltage range0 V to 600 V
Current range1 mA to 120 A, 10 mA to 200 A, 60 mA to 600 A
Phase measurement0 to 359.99
Frequency measurement40 Hz to 70 Hz
Power factor measurement-1 to 1
Energy pulse output25000
Energy pulse input1 to 25000
Communication portUSB & Bluetooth port
LCD3.5 in (8.89 cm) touch TFT color LCD
Dimensions8.8 in x 2.4 in x 1.4 in (22.5 cm x 6.1 cm x 3.8 cm)
Weight17.63 oz (500 g)
Scroll to Top